| ECU-1911-R0CAE |
| Analog Input |
Accuracy |
Voltage : ± 0.1 %, Current : ± 0.2 % |
| Digital Input |
Channels |
32 |
| Connector |
Terminal Block (#14 ~ 22 AWG) |
| I/O Type |
Sink |
| Isolation |
3000 VDC |
| Wet Contact |
Logic 0: 0 ~ 10 V, Logic 1: 19 ~ 30 V |
| Digital Output |
Connector |
Terminal Block (#14 ~ 22 AWG) |
| Contact Rating |
AC: 5A @ 250 V; DC: 30 V @ 5 A (Resistive Load) |
| I/O Type |
Power Relay Form A |
| Isolation |
500 VDC |
| General |
OS Support |
Windows CE 5.0 |
| Power Consumption |
<10 W (Typical) |
| Power Requirement |
24 VDC (Typical) (10 VDC Min ~ 30 VDC Max) |
| System Hardware |
CPU |
Xscale @ PXA-270 520MHz |
| Memory |
Onboard 64 MB SDRAM/ 32 MB Flash |
| Storage |
1 x type I/II Compact Flash slot |
| Analog Input |
Channels |
8 differential |
| Drift |
±25 ppm/° C |
| Input Impedance |
700 kΩ |
| Input Range |
0 ~ 150 mV, 0 ~ 500 mV, 0 ~ 1 V, 0 ~ 5 V, 0 ~ 10 V, 0 ~ 15 V, ±150 mV, ±500mV, ±1 V, ±5 V, ±10 V,±15 V, ±20 mA, 4 ~ 20 mA |
| Resolution |
16 bits |
| Sampling Rates |
10 Hz/sec (total) |
| Environment |
Humidity |
5 ~ 95% @ 40°C (non-condensing) |
| Temperature (Operating) |
-20 ~ 70°C (-4 ~158°F) @ 5 ~ 85% RH |
| Temperature (Storage) |
-30 ~ 80° C (-22 ~ 176° F) |
| I/O Interface |
LAN |
2 x 10/100 Base-T RJ-45 ports |
| Serial Ports |
4 x RS-232, 2 x RS-232/422/485 with DB9 connectors Automatic RS-485 data flow control |
| USB Port |
1 x USB, OpenHCI, Rev. 1.1 compliant |